WhatApp

Product

DGB3LE-40AFD

DGB3LE-40AFD series of arc fault protection derivces are assembled by small circuit breaker, tripping mechanism, leakage and arc detection module.DGB3- 40AFD series of arc fault protection devices have the functions of short circuit protection, overload protection, leakage protection and arc fault protection. It detects the current of zero sequence current transformer through chip detection program, realizes the function of leakage protection, and detects arc fault through chip detection program, that is, it will disconnect power supply and play the role of arc fault protection. According to the China Fire Yearbook, the proportion of electric fire in the total fire is increasing year by year. However ,70% of the electric fire is caused by fault electricity, DGB3-40AFD series of arc fault protection devices can effectively avoid the fire caused by arc fault.

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB Enterprise code
3LE Design code
40AFD Frame rated current (A) AFD: Arc Fault Detect Device
1P+N Number of poles: 1P+N
C Instantaneous Trip characteristic type: B, C, D
40 Rated current (A) 6,10,16,20,25,32,40
30mA Rated residual action current (mA)
DGB3LE-40AFD

Functions

  • DGB3-40AFD arc fault protection devices is suitable for fault arc, overload,short circuit and leakage protection of lighting distribution system and power distribution system branch large load equipment with rated current of 40A and


Normal conditions of use

Storage temperature-5 or +40. Average daily maximum temperature is +35.No more than 2000 m, relative humidity 40°C at 50% m , 40°C at 90%m.


Characteristics of products

DGB3LE-40AFD series of arc fault protection device include leakage protection,fault arc protection, overload protection and short circuit protection functions.DGB3LE-40AFD series of arc fault protection appliances leakage tripping characteristics as shown in Table 1 below:

Table 1

Model In(A) I △ n Break time and non-drive time limited value
I△n 2I△n 5I△n  
 

DGB3LE-40AFD

 

Any Values

>0.03 0.3 0.15    

Maximum breaking time

0.03 0.3 0.15  
<0.03 0.3 0.15 0.04

The arc fault protection function of DGB3LE-40AFD series of arc fault protection devices mainly includes the arc fault protection detection unit, which detects and identifies the fault arc in the line and sends out the tripping signal. The DGB3LE-40AFD main contact is automatically converted from the closed position to the disconnected position, thus disconnecting the fault line.

Action judgement and breaking time maximum value of a 230V rated arc fault protection device is shown in Table 2, Table 3.

Table 2 ,maximum value of ADDF action judgment under high arc current below 40A

Test arc current (Effectiv Value) 3A 6A 13A 20A 40A
Maximum segmen time 1S 0.5S 0.15S 0.25S 0.12S

Test arc current is the expected current before burning in test circuit.

Table 3,maximum value of ADDF action judgment under high arc current above 40A

Test arc current (Effectiv Value) 75A 100A 150A 200A 300A 500A
N 12 10 8 8 8 8

N is half wave number at rated frequency.

DGB3LE-40AFD overcurrent protection function of a series of arc fault protection devices. When the circuit current exceeds the rated current of the product,bending deformation occurs DGB3LE-40AFD the hot stripper system in the series arc fault protection appliances to drive the main contact from the closed position to the disconnected position. Thus disconnecting the current.DGB3LE-40AFD arc fault protection appliances overcurrent tripping characteristics as shown in Table 4

Table 4 DGB3LE-40AFD Overcurrent tripping characteristics

 

Serial Number

Detail rated current

InA

Starting state Test current Tripping time Expected result  

Remarks

1  

≤40

Cold sate 1.13 :1h Non-tripping
 

2

After on time experienm  

1.45

 

<1h

 

Tripping

Current increase to index value within 5s
3 ≤32  

 

 

Cold state

2.55 1s<t<60s Tripping
>32 1s<t<180s
4  

≤40

5 ≤0.1s Non-tripping Closing auxiliary contact to current
5 10 <0.1s Tripping Closing auxiliary contact to current


Product and installation dimensions(MM)


Installation guide


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB3LE-40AFDseries, such as: DGB3LE-40AFD Arc Fault Detect Device operated circuit breaker
  • Trip type, such as: C type
  • Number of poles of product, such as 1P+N
  • Rated current, such as 32A
  • Rated residual operating current, such as: 30mA
  • type wave form of earth leakage sensed such as: A type
  • Order quantity, such as: 1000 units
  • Specified as: DGB3LE-40AFD C32 1P+N 30mA A type 1000 units


Inquiry

    Technical Data

    Product name DGB3LE-40AFD
    Standards AFDD as per IEC/EN-62606, RCBO as per IEC/EN-61009
    Certificate CE, CB
    Electrical characteristics
    Number of poles 1P+N
    Rated frequency (Hz) 50/60
    Frame current (A)                                        Inm 40
    Rated current (A)                                         In 6,10,16,20,25,32,40
    Rated voltage (V) AC230V
    Rated insulation voltage (V) Ui 500
    Rated impulse withstand voltage (kV) Uimp 4
    Rated short-circuit breaking capacity (kA)   Ics 6
    Rated short-circuit breaking capacity (kA)   Icn 6
    Instantaneous trip characteristics B,C,D
    Trip form Thermal, magnetic and Lekage trip, arc detected trip
    Pollution level 2
    Rated residual action current (mA) 30
    Max. breaking time at the rated residual current 0.1s
    Residual current type A
    Overvoltage protection: Uvo=280V±5% YES
    Electrical and mechanical accessories /
    Mechanical properties
    Electrical life 4000
    Mechanical life 10000
    Protection grade IP20
    Indicator window Contact status indication and Leakage indication, LED indication for Arc detection
    Normal operation conditions and installation characteristics
    Storage temperature -35℃ ~ +70℃
    Installation site altitude ≤ 2000m
    Terminals Fixed with screw
    Maximum wiring capacity 16mm2
    Maximum limit torque Nm 2.5
    Installation category Class Ⅱ , Ⅲ
    Installation method 35mm standard rail
    Incoming method Upper and lower

    Related Products

    Call To Action

    Satisfaction is Our Motto

    Specializing in manufacturing quality low voltage electricals since 2002