WhatApp

Product

DGB3LE-40B

DGB3LE-40B series Residual current circuit breaker with overload protection is mainly used in AC 50Hz with rated working voltage 230V and with rated current up to 40A. In case of personal electric shock or when the grid leakage exceeds the specified value, the residual current circuit breaker can quickly cut off the power supply in a very short time for protection of the safety of people and electrical equipment and also for infrequent changeover of line and infrequent start of motor. This   product is suitable for various places such as industry, business, and high-rise residential buildings

 

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB3LE Enterprise code
40B Frame rated current (A) B:B type
2P Number of poles: 1P+N
C Instantaneous Trip characteristic type: B, C, D
40 Rated current (A) 6,10,16,20,25,32,40
30mA Rated residual action current (mA)
DGB3LE-40B

Tripping Characteristic Curves

IEC61009-1/IEC62423:2009


Product and installation dimensions(MM)

DGB3LE-40B should be installed on DIN rail terminal and can be connected to the wire less than 16mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB3LE-40B series, such as: DGB3LE-40B residual current operated circuit breaker
  • Trip type, such as: C type
  • Number of poles of product, such as 1P+N
  • Rated current, such as 32A
  • Rated residual operating current, such as: 30mA
  • type wave form of earth leakage sensed such as: A type
  • Order quantity, such as: 1000 units
  • Specified as: DGB3LE-40B C32 1P+N 30mA A type 1000 units

 


Inquiry

    Technical Data

    Product name DGB3LE-40B
    Standards IEC61009-1/IEC62423:2009
    Certificate CE, CB
    Electrical characteristics
    Number of poles 1P+N
    Rated frequency (Hz) 50/60
    Frame current (A)                                        Inm 40
    Rated current (A)                                         In 6,10,16,20,25,32,40
    Rated voltage (V) AC230V
    Rated insulation voltage (V)                      Ui 500
    Rated impulse withstand voltage (kV)     Uimp 4
    Rated short-circuit breaking capacity (kA)   Ics 6
    Rated short-circuit breaking capacity (kA)   Icn 6
    Instantaneous trip characteristics B,C,D
    Trip form Thermal, magnetic and Leakage trip
    Pollution level 2
    Rated residual action current (mA) 30/50/100/300
    Max. breaking time at the rated residual current 0.1s
    Wave form of earth leakage sensed B
    Overvoltage protection: Uvo=280V±5% /
    Mechanical properties
    Electrical life 4000
    Mechanical life 10000
    Protection grade IP20
    Indicator window Contact status indication and Leakage indication
    Normal operation conditions and installation characteristics
    Storage temperature -35℃ ~ +70℃
    Installation site altitude ≤ 2000m
    Terminals Fixed with screw
    Maximum wiring capacity 16mm2
    Maximum limit torque Nm 2.5
    Installation category Class Ⅱ , Ⅲ
    Installation method 35mm standard rail
    Incoming method Upper and lower
    Action performance of circuit breaker
      Rated current Start state Specified time Expected results Remarks  
     

     

    Thermal Release

    6-40A Cold state 1.13 In t ≤ 1h Not trip  
     

    6-40A

     

    Hot state

     

    1.45 In

     

    t < 1h

     

    Trip

    Immediately after a) test, the current increases to the specified value within 5s.
    6-40A Cold state 2.55 In 1s < t < 60s Trip  
     

     

     

    Magnetic Release

     

     

    6-40A

     

     

    Cold state

    3In(B type)  

     

    t ≤ 0.1s

     

     

    Not trip

     

    Turn on the auxiliary switch for making current

    5In (C type)
    10In(D type)
     

     

    6-40A

     

     

    Cold state

    5In(B type)  

     

    t < 0.1s

     

     

    Trip

     

    Turn on the auxiliary switch for making current

    10In(C type)
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A) Nominal cross area of copper wire (mm²)
    6 1.5
    10 2.5
    16, 20 4
    25 6
    32 10
    40 16