WhatApp

Product

DGB7-125

DGB7-125 miniature case circuit breaker is used in AC 50/60 line with rated voltage 230V (for 1P) or 400V (for 2P/3P/4P) and rated current up to 125A for overload and short-circuit protection. It can also be used for infrequent ON/OFF switching of the line under the normal operation. The circuit breaker is characterized by artistic shape, small size, light weight, excellent and reliable performance, high breaking capacity, quick tripping, and rail-mounted installation

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DGB7 Enterprise code
125 Breaking capacity : 10kA Frame rated current (A)
1P Number of poles: 1P, 2P, 3P, 4P
C Instantaneous Trip characteristic type: B,C, D
100 Rated current (A) 32,40,50,63,80 100,125
OF2 OF2 (auxiliary) MX2 (Shunt release)
DGB7-125

Tripping Characteristic Curves

IEC60947-2 / IEC60898-1


Product and installation dimensions(MM)

DGB7-125 should be installed on DIN rail terminal and can be connected to the wire less than 50mm2


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when ordering.
  • Order example: DGB7-125series miniature circuit breaker, breaking capacity 10kA, C-type instantaneous
  • release, rated current 100A, two-pole, 1000
  • Specified as: DGB7-125 C100 2P 1000 units


Inquiry

    Technical Data

    Product name DGB7-125
    Standards IEC60947-2 / IEC60898-1
    Certificate KEMA, CE, CCC, CB
    Electrical characteristics
    Number of poles 1P,2P,3P,4P
    Rated frequency (Hz) 50/60
    Frame current (A) Inm 125
    Rated current (A) In 32,40,50,63,80,100,125
    Rated voltage (V) AC240V/415V  (230V/400V)
    Rated insulation voltage (V) Ui 690
    Rated impulse withstand voltage (kV)Uimp 4
    Rated short-circuit breaking capacity (kA)Ics 6/7.5
    Rated short-circuit breaking capacity (kA)Icn 6/10
    Instantaneous trip characteristics B,C,D
    Trip form Thermal magnetic trip
    Pollution level 2
    Electrical and mechanical accessories OF2 (auxiliary)/MX2 (Shunt release)
    Mechanical properties
    Electrical life 1,500(In≤100A), 1,000(In>100A)
    Mechanical life 8,500(In≤100A), 7,000(In>100A)
    Protection grade IP20
    Indicator window Contact status indication
    Normal operation conditions and installation characteristics
    Storage temperature -35℃ ~ +70℃
    Installation site altitude ≤ 2000m
    Terminals Fixed with screw
    Maximum wiring capacity 50mm2
    Maximum limit torque Nm 3.5
    Installation category Class Ⅱ , Ⅲ
    Installation method 35mm standard rail
    Incoming method Upper and lower
    Action performance of circuit breaker
      Rated current Start state Specified time Expected results Remarks  
     

     

     

    Thermal Release

    32-125A Cold state 1.05 In t ≤ 2h Not trip  
     

    32-125A

     

    Hot state

     

    1.3 In

     

    t < 2h

     

    Trip

    “Immediately after a) test, the current increases to the specified value within 5s.”
    32-63  

    Cold state

     

    2.55 In

    1s < t < 60s Trip  
    80-125 1s < t < 120s Trip  
     

     

    Magnetic Release

     

    32-125A

     

    Cold state

    5In (C type)  

    t ≤ 0. 2s

     

    Not trip

    Turn on the auxiliary switch for making current
    10In(D type)
     

    32-125A

     

    Cold state

    10In(C type)  

    t < 0. 2s

     

    Trip

    Turn on the auxiliary switch for making current
    14In(D type)
    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A) Nominal cross area of copper wire (mm²)
    32 6
    40-50 10
    63 16
    80 25
    100 35
    125 50

     