WhatApp

Product

DGGQ3-63

DGGQ3-63 self-recovery over-voltage and under-voltage protector (hereinafter referred to as the protector) is suitable for load line with AC voltage single-phase 230V/three-phase 400V, frequency 50/60 Hz, rated operating current 63A and below. When the circuit  voltage is abnormal due to single-phase (three-phase) over-voltage caused by the neutral ine fault in the circuit, serious unbalanced three-phase load, too large line resistance, phase loss or high-order harmonics, the protector can automatically disconnect the load-side power supply, thereby preventing damage to the electrical equipment and realizing the protection of the electrical equipment. Also, the protector can automatically detect the line voltage, and can automatically close when the line has a normal voltage, thereby restoring the power supply to the electrical equipment. The product shall be used in series with a circuit breaker, mainly used in the incoming branch box or other power distribution lines to be protected in the civil and commercial buildings.

  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DG Enterprise code
GQ3 GQ: Over voltage and Undervolatge 3: Third Generation
1P+N Number of poles: 1P+N, 3P+N
63A Rated current (A) 20,25,32,40,50,63
DGGQ3-63

Overvoltage action time curve


Wiring connection


Product setting


Overall & Installation Dimensions


Order information

  • When ordering, please specify the product model, working current specification, wiring method, and order For example: To order 1000 sets of DGGQ2-63 self-recovery over-voltage protector with rated current 63A, 1P+N, bottom incoming, please specify: DGGQ2-63 1PN 63A, bottom-in and top-out, 1000 units.


Inquiry

    Technical Data

    Electrical characteristics
    Product name DGGQ3-63
    Rated current (A) 20,25,32,40,50,63
    Rated voltage (V) 230V (1P+N), 400V (3P+N)
    Number of poles 1P+N / 3P+N
    Rated impulse withstand voltage Uimp (kV) 4
    Overvoltage action cut-off value (V) AC >275V
    Overvoltage recovery value (V) AC 240-265V
    Undervoltage action cut-off value (V) AC 50-160V
    Undervoltage recovery value (V) AC 185-205V
    Power transmission delay after power failure (s) 30±5s
    Undervoltage trip time 0.6s < t < 5s
      275V 3s < t < 15s
     

    Overvoltage trip time

    300V 1s < t < 3s
    350V 0.25s < t < 0.75s
    400V 0.1s < t < 0.2s
    Power (W) ≤1W
    Mechanical properties
    Electrical life ≥10000
    Mechanical life ≥100000
    Indicator window Digital indicator
    Normal operation conditions and installation characteristics
    Storage temperature -25~+55ºC
    Installation altitude < 2000m
    Installation category Class Ⅱ , Ⅲ
    Installation method 35mm standard rail
    Max. limit torque 3.5N.m
    Incoming method Top in and bottom out, bottom in and top out
    Protection grade IP20
    Electromagnetic compatibility (EMC)  
    Electrostatic discharge 8kV (air discharge) / 6kV (contact discharge)
    Radio frequency radiation 3V/m 80MHz ~ 1000MHz
    Transient shock 4kV 2.5kHz
    Surge ±4kV
    Radio frequency conducted interference 3V 0.15 ~ 80MHz
    Voltage sags and interruptions Class 2

    Related Products

    Call To Action

    Satisfaction is Our Motto

    Specializing in manufacturing quality low voltage electricals since 2002