WhatApp

Product

DGL2-63B

DGL2-63B series residual current circuit breaker (hereinafter referred to as the circuit breaker) is mainly used in AC 50Hz circuit with rated voltage 400V and rated current up to 63A. In case of personal electric shock or when the grid leakage exceeds the specified value, the residual current circuit breaker can quickly cut off the power supply in a very short time for protection of the safety of people and electrical equipment and also for infrequent changeover of line and infrequent start of motor. This product is suitable for various places such as industry, business, and high-rise residential buildings

CB certifications CE certifications KEMA certifications
  • Type designation
  • Product Information
  • Inquiry
  • Technical Data
  • Related Products
DG Enterprise code
L2 Magnetic type residual current circuit breaker
63B F rame rat ed current (A) B:wave form is B type
2P Number of poles: 2P/ 4P
40 Rated current (A) 16,20,25,32,40,50,63
30mA Rated residual action current (mA)
DGL2-63B

Wiring diagram


Product and installation dimensions(MM)


Order information

  • Please specify the product model and specification, and the type, rated current, number of poles, and order quantity of the instantaneous release when Ordering.
  • Order example: DGL2-63B series, such as: DGL2-63B residual
  • current operated circuit breaker
  • Number of poles of product, such as 2P
  • Rated current, such as 32A
  • Rated residual operating current, such as: 30mA
  • type wave form of earth leakage sensed such as: A type
  • Order quantity, such as: 1000 units
  • Specified as: DGL2 -63B 32A 2P 30mA AC type 1000 units

 


Inquiry

    Technical Data

    Product name DGL2-63B
    Standards IEC61008-1/IEC62423:2009
    Certificate Kema CE, CB
    Electrical characteristics
    Number of poles 2P/4P
    Rated frequency (Hz) 50/60
    Frame current (A)Inm 63
    Rated current (A)In 16,20,25,32,40,50,63
    Rated voltage (V) AC240V/415V  (230V/400V)
    Rated insulation voltage (V)Ui 500
    Rated impulse withstand voltage (kV)Uimp 4
    Rated short-circuit breaking capacity (kA)Ics 7.5
    Rated short-circuit breaking capacity (kA)Icn 10
    Trip form Leakage trip
    Pollution level 2
    Rated residual action current (mA) 30100/300
    Max. breaking time at the rated residual current 0.1s
    Wave form of earth leakage sensed B
    Mechanical properties
    Electrical life 6000
    Mechanical life 10000
    Protection grade IP20
    Indicator window Contact status indication
    Normal operation conditions and installation characteristics
    Storage temperature -35℃ ~ +70℃
    Installation site altitude ≤ 2000m
    Terminals Fixed with screw
    Maximum wiring capacity 25mm2
    Maximum limit torque Nm 3.5
    Installation category Class Ⅱ , Ⅲ
    Installation method 35mm standard rail
    Incoming method Upper and lower

    DGL2-63B should be installed on DIN rail terminal and can be connected to the wire less than 25mm2

    Wiring: Suitable for wire connection of 16mm2 The screws according to the tightening torque 3.5N·m
    Rated current (A) Nominal cross area of copper wire (mm²)
    6 1.5
    10 2.5
    16, 20 4
    25 6
    32 10
    40, 50 16
    63 25